The thermaliQ:HB2 treatment group is used to demineralize raw water in the initial filling or replenishment of heating systems. The mixed-bed resin in the filling cartridge desaliQ:HB2 removes all salts from the water. This fully demineralized water has a low conductivity and thus reduces galvanic corrosion between metals of different voltage series. The conductivity measuring cell monitors the demineralization products connected to the treatment group. The desaliQ:HB2 filling cartridge is included in the scope of delivery. The conductivity measuring cell has three LEDs. If the conductivity is below 10 uS/cm, the green LED flashes; between 10 and 50 uS/cm, the yellow LED lights up; and at 50 uS/cm or more, the red LED lights up to indicate that the desalination unit needs to be replaced.
Structure:
- Brass casing
- Plastic bell
- Vent valves
- inlet-side shut-off valve
- LF measuring cell
Technical data:
Connection: DN 15
Thread: 1/2" AG
Capacity <10 uS/cm x cbm : 25 uS/cm x cbm <50 uS/cm x cbm : 40 uS/cm x cbm
Operating pressure max. : 6 bar
Filling capacity (without cartridge): 2.65 cbm/h at 1.5 bar
Filling capacity with desaliQ:HB2: 0.2 cbm/h
Installation length with screw connection: 265 mm
without screw connection: 160 mm
Maximum water temperature: 30 degrees Celsius
Shipping weight: | 2,89 kg |
There are no reviews yet.