Automatic filter pureliQ:AD32 with pressure reducer
for installation directly after the water meter system to protect the domestic
water installation in accordance with DIN EN 806-2.
- DVGW certified
- Automatic filter with pressure reducer according to
DIN EN 13443-1, 19628 and DIN EN 1567,
consisting of:
Electric motor with control electronics,
membrane keypad, plug-in power supply and
supercaps for the power supply in the event of a
power failure to ensure that the
backwash valve closes. Optional setting
of the backwashing interval of 7, 30, 60 and
90 days with LED display. Factory
setting: 60 days. Manual backwashing
possible by pressing the manual button for 3 seconds.
Closed device surface, making it
easy to clean from the outside. Well-thought-out
structure with viewing window for
determining the degree of soiling of the filter element.
The covers protect
the filter bell and the filter element
from UV light.
Thanks to pre-installed components,
commissioning can be carried out in just a few minutes.
Convenient installation in all situations
thanks to rotatable click connection flange,
for adjusting the flow direction
according to local conditions.
Water meter screw connection made of dezincification
resistant brass.
Flexible duct connection with integrated
free outlet, precise installation for perfect
tightness.
Flow-optimized pressure reducer,
adjustable from 1 to 6 bar, with a
maintenance-friendly manometer. Ergonomically
shaped pressure reducer handwheel for
setting the desired line pressure.
Factory setting of the initial
pressure to 4 bar.
Clearly legible interval display for
filter regeneration.
Filter element made of stainless steel for long-term
use.
Residue-free filter cleaning through
water swirl with innovative Grünbeck
vortex technology.
Technical data:
Connection: 1 1/4" R
Flow rate
according to DIN EN 1567: 5.8 cbm/h
Nominal pressure: PN 16
Operating pressure: 2-16 bar
Max. water temperature: 30 degrees C
Filter fineness: 100 µm
Installation length without
screw connection: 100 mm
Installation length with
screw connection: 191 mm
Overall height: 405 mm
Mains connection: 100-240 V/
50-60 Hz
Electrical power
consumption
operating= max./standby: 2/0.075 W
Degree/class of protection: IP54/III