can be installed in all types of solar heating systems with variable or constant volume flow, but must not be controlled by an external speed controller that changes the supply voltage. The speed can be controlled by a pulse-width modulated signal (PWM signal) supplied by the solar system controller to optimize the solar energy yield and the system temperature. This significantly reduces the power consumption of the pump. If no PWM signal is available, the ALPHA SOLAR can be set to a constant speed. It is then only switched on and off by the controller.
Technical data:
Operating pressure: Maximum 1.0 MPa (10 bar)
Minimum supply pressure: 0.05 MPa (0.5 bar) at 95 °C media temperature
Maximum media temperature: 2 to 110 °C at 70 °C ambient temperature
Degree of protection: IPX4D
Motor protection: no external motor protection required
Approval and labeling: VDE, CE
Water/propylene glycol mixture: the propylene glycol content in the water must not exceed 50%
Note: when using a water/propylene glycol mixture, the flow rate is reduced due to the higher viscosity
Product features:
• 4 constant speeds
• Defrosting screw
• PWM profile C (solar systems), the PWM signal is a method for generating an analog signal from a digital source
• Low energy efficiency index (EEI = 0.20)
• Maintenance-free
• Low noise
• Very easy to install