Non-intrinsically safe leak detector of class II (EN 13160-1). Consisting of a control unit, a leak indicating liquid tank (white LAG tank) and a probe. Control unit with operating and alarm displays, visual/audible alarm, test button and increased interference protection. The audible alarm can be stopped with the acknowledge button. A mounting frame is included for installation in control panels; a sealing set (IP 54) is available for harsh operating conditions. The LAG tank is a control tank and an expansion tank at the same time. For above-ground tanks, the ratio of usable capacity to the total amount of the leak-indicating liquid may not exceed 1:35. If the ratio is higher, an additional container must be used. Version LAG-13 KR with potential-free relay contact for connection to permanent warning devices (e.g. horns, event reporting system EMS or additional alarm device ZAG 01).
Temperature range
- Ambient temperature: -5/+55 °C
- Storage: -10/+60 °C
Supply voltage
- AC 230 V
Signal unit
- Wall-mounted enclosure made of impact-resistant
- Plastic (ABS)
- W x H x D: 100 x 188 x 65 mm
- Degree of protection: IP 40 (EN 60529)
Switching outputs (LAG 13 KR)
- Relay outputs: 1 potential-free NO contact
- Contact load: AC 250 V, 2A
Container
- Plastic, white
- W x H x D: 300 x 380 x 150 mm
- Capacity / total capacity: 4.5 l / 9.7 l
- Outlet: G¾
- Protection type: IP20 (EN 60529
General building inspectorate approval
- Z-65.24-380
Figure: Afriso
Shipping weight: | 0,49 kg |