PTC thermistor-based limit indicator, consisting of mechanical level meter MT-Profil R, probe, screw-in unit, fitting for wall mounting and cable between probe and fitting. GWG connection fitting type 905 yellow is impact-resistant, shock-resistant and dimensionally stable. Optionally, GWG filling cap type 906 (art. no. 20430) can be used.
Design according to EN 13616 (TRbF 511/512)
Fitting
- Type 905 yellow for wall mounting
Process connection
- Screw-in body G1½
Medium
- Fuel oil EL (DIN 51603-1)
- Diesel fuel (EN 590)
- FAME 100% as bio heating oil (EN 14213)
- FAME 100% as biodiesel (EN 14214)
Measuring range: filling level (tank height)
- Turning scale 0/150 and 0/250 cm
Setting range for limit indicator
- 80 to 338 mm
Probe length
- 360 mm
Cable length
- 5 m
General building approval
- Z-65.17-182
Figure: Afriso
Shipping weight: | 0,78 kg |